Skip to content

2.4 Meter Wiring

2.4.1 Macnaught MetersLink

There are several types of Macnaught meters.

We have had superior results with MX range of meters.

Most Macnaught meters and registers come with Pulse, or Hall Effect as:

  • Either of

  • Both Of

  • Dual

Where odd behavior is detected or low quality signal/noise from the meter output, it may need to use a combination of the pullup/pulldown resistors built into the Fuellox design.

2.4.2 kFactorsLink

Machanught usually calibrates the meter and publishes its kFactor in the format of Pulses per Litre.

To calculate the Fuellox kFactor simply divide 1 by the published figure and enter the resulting kFactor to 6 decimal places.

On occasion further calibration may not be required.

2.4.3 Wiring GuideLink

Macnaught Wiring Diagram

2.4.4 Flomec MetersLink

Flomec meters may also present as GPI branded meters.

flomec reed switch wiring diagram

flomec installation diagram

2.4.5 Gespasa MetersLink

We have had limited success with Gespasa meters at this point and until further integration testing they are not recommended or supported.

2.4.6 Liquip MetersLink

Liquip meters are mostly found on bulk dispensing pumps such as Ebs Ray, Alfons Haar etc.

You will generally find they are used in mobile applications but sometimes in large off-road refuelling facilities such as mines, tank farms and for very large machinery refueling.

Fuellox integrates positively with these meters where an operator can actuate the pump via the Fuellox relay.

Where an Electronic Register is used, see Section 2.4.7

Where a Mechanical Register is used, see Section 2.4.11

2.4.7 DFV RangeLink

The meter needs to have the output pulse connected, prior to calibration by the Liquip authorised agent. Electronic Pulse out, to Fuellox J5, Pins 2 & 3 as per typical pulse meter reed type installations.

2.4.8 Piusi MetersLink

Piusi meters mostly come with a Reed effect, in 2 wire format.

Piusi Reed SwitchLink

Piusi K24 and Turbinox each use a brown and blue wire. We have several units running with these meters.

Piusi installation diagram

2.4.9 PS100 Pulse MeterLink

Used as a meter transmitter for/with a mechanical register. The PS100 is a medium quality part imported from China. Note this meter does not include a wet seal and installation to should be completed by an experienced installer. Contact the Fuellox team for an appropriate referral from your region.

Depending on the register type it may be nesecary to discard the register, and use the shaft from the meter. Under such circumstances, ensure the meter body is sealed and that fuel can not escape the meter assembly.

Warning

Modification of any meter may result in changes to the calibration requirements, performance and repeatability.

This meter comes with dual pulse outputs, however only 1 shall be used with Fuellox.

PS100 wiringLink

PS 100 Meter Fuellox Description
Red J8 Pin 1 +12 V DC
Black J8 Pin 2 0 V DC
Yellow J5 Pin 2 Pulse Signal
Blue Exclude Spare pulse channel

A wiring diagram is available : PS100 Wiring Diagram Right click and Save As to download or click to open in new tab.

Installation StepsLink

  1. Locate the main shaft coming from the Mechanical meter register.
  2. Build a mounting assembly that locates the pulse meter body to the shaft position
  3. Build and install a shaft to match the register shaft to the pulser shaft
  4. Remove the wire connector and connect the cables as per above. Be sure to use shielded cable at all times
  5. Commission the meter and test with the Fuellox system
  6. Calibrate the Fuellox pulse signal to the existing meter register.

2.4.10 Macnaught MX with ERALink

The Macnaught meter can facilitate an additional display by integrating the Machanguth ERA display. Its recommended that a single meter be used where a display and pulse is required. The use of 2 meters (ie 1 mechanical and 1 digital) can lead to confusion for operators and calibration complexity.

The main signal wire enters the ERA Display and is bridged to the Fuellox

Note

Macnaught recommend a dual hall/reed type meter, however this wiring guide is for the 1RA type meters, with a sinlge Hall effect. The Reed effect is no used.

ERA WiringLink

Power MX-25 ERA Fuellox
12V +ve none Pin 1 J8 Pin 1
12V -ve none Pin 0 J8 Pin 2
Pulse from MX-25 ERA
Green Pin 9
Yellow Pin 10
Red Pin 11
Blue Abandon
White Abandon
ERA Fuellox
5 J5 Pin 3
6 J5 Pin 2

Several configuration steps are required to ensure the ERA displays correctly. When stuck, consult the Macnaught service team, during business hours via the head office technical team.

Detailed ERA Wiring Diagram Right Click and 'Save As'

ERA ConfigurationLink

The ERA display can be difficult to set up with the Fuellox system. Go through the ERA Menu and adjust each parameter as follows. Macnaught ERA Manual Right Click and 'Save As'

Section Setting Context Value
1 TOTALS
1.1 Units Display units L
1.2 Decimals Decimal places on display 0
1.3 kFactor Litres per pulse, from calibration certificate See Meter documentaion
1.4 Decimal kFactor Decimal places in kFactor 6
2 FLOWRATES
2.1 Units Display units L
2.2 Time Time display for flow rate
2.3 Decimals 222
2.4 kFactor See 1.3
2.5 decimals kFactor 6
2.6 Calc/pulse 10
2.7 cut off 30
3 DISPLAY
3.1 Function total
3.2 Light 100
4 POWER MANAGEMENT
4.1 LCD New 1 sec
4.2 Batt Mode OP
5 FLOWMETER
5.1 Signal NPN LP
6 ANALOGUE OUTPUT Leave as default
7 IMPULSE
7.1 Pulse Width Output signal width 0.01
7.2 Decimals decimal places of Impulse settings 3
7.3 Amount vol per pulse 0.027
8 COMMUNICATION Leave as defaults
9 OTHERS Meter Parameters

2.4.11 Veeder Root 7671 family of pulsersLink

Veeder Root pulsers operate a hall effect. Fuellox requires a single channel pulse from the 7671. Veeder Root also offer a family of meters that integrate directly with the pump. These 3 channel meters are not suitable for use diretly with Fuellox.

In some circumstances the 7671 can suffer from noise interferrance, such as when used in a confined space with a large 3 phase motor and pump. In these cases additional wiring is required.

Wiring DiagramLink

Veeder Root 7671 installation diagram

Earthing of MeterLink

The Veeder Root pulser must also be grounded as per the OEM directions Veeder Root 7671 earthing diagram

Jumper settingsLink

Apply jumpers to SK5 and SK7 for this meter type. See Pull up & Pull down resistors.

Wiring detailLink

Item Part Label Pin Description
1 Fuellox J5 1 Meter Power 12V DC
1 Fuellox J5 2 Meter Signal
1 Fuellox J5 3 Meter 0V (Floats)
2 Fuellox J3 2 Wire shield to 0V DC
3 VR 7671 - GND to Fuellox J5-3
3 VR 7671 - CH 1 to Fuellox J5-2
3 VR 7671 - V+ to Fuellox J5-1
4 Shielded Cable - Cable 3 Core, MUST be shielded
5 Shielded Cable - Shield 3 Core, MUST be shielded
6 VR 7671 Earth 3/16 screw Suitable Earth to ground stake

Pulse meter configurationLink

7671 meters will produce either 10, 50 or 100 pulses per Litre and depends largely on the configuration of the mechanical meter, and pump type.

Start with a device kFactor of 0.1 and calibrate against the mecahnical meter. Ensure the meter register has been calibrated by an authorised service technican. Note: Once the Mechanical meter has been calibrated the Fuellox system should not need to be recalibrated. The relationship to meter revolutions should be maintained.

Cable recommendation:Link

We have had excellent results with Jaycar 4 Core, Screened Cable Part WB1540. Where a screened cable is not used, system reliability and accuracy is not assured. Warranty does not apply for incorrectly installed meters.

WB1540 Screened Cable

2.4.12 Other MetersLink

We can and will test other meter integrations only where our technical team can access the hardware units for testing.

Alternatively you can lone or provide free issue samples to the Fuellox team for evaluation and testing. Costs may apply.