2.12 System CommissioningLink

Some pointers.Link

Your Fuellox unit must have a k-Factor applied to the actual hardware to enable the pump channel. Without that, the pump won't start.

TroubleshootingLink

Can't see device in the Fuellox AppLink

MAke sure the Fuellox unit is assigne to your account. Check your Dashboard in Devices for the serial number. If its there the unit is in your account, if not check with the help desk.

Wrong Fluid MessageLink

You must select an Equipment/Compartment so the app knows what fluid to search for.

Select the Equipment and Compartment. Now connect to the Fuellox unit.

If you still see the Wrong Fluid message alert the help desk.

Can't ConnectLink

Try unpairing the BLE device and repair once again.
See Re-Pair BLE here.

New settings don't take affectLink

Once the Device has been configured via the app it must be restarted. Failure to power cycle the hardware may prevent new settings from working.

Power cycle your unit for 20-30 seconds. If you are using a high capacitance power supply longer time may be needed.

Power up the unit and try again.

Note: We recommend all Fuellox units have a mains power isolator so thaty can be turned off.

Trouble with Estop, or Nozzle SwitchLink

Some older version of Fuellox App had issues modifying the instrumentation parameters

Info

Make sure you have Fuellox App version 0.9450 or higher to apply the hardware device settings.

Level probe not workingLink

Make sure the device level attributes are correctly applied. In the Device config set:

Feature Description Default Value unit
Level Options
Level Installed Level instrument installed True Boolean
Max Level Max hight of liquip in mm. usually same as Safe Fill 3000 mm max
Max Analogue Max analogue value 20 mA max

Typical Analog max values, guide only

Tank Height (mm max) Analog Max
3,000 20
2,700 18
2,400 16
1,200 10
1,000 7