Skip to content

4.2 Callibration

Most Pulse meters have a factory kFactor.They generally require calibration during commissioning. The Fuellox team will adjust the kFactor for you during commissioning. Take a calibration jug, and fill to the top. That Transaction can be used to calibrate the system.

Option 1Link

Calculate the new kFactor Installer fills a 15L jug. Fuellox reports 13L. Factory kFactor = 0.05 Calculate the number of pulses. 13L ÷ 0.05 = 260 pulses. 15L ÷ 260 pulses = new kFactor = 0.05769.

Option 2Link

Provide the Fuellox team the date, and time of the transaction or Transaction ID if known, along with the real Volume and the Fuellox team shall do the calculation and adjustment. Once the kFactor has been changed the app will need to be re-sync for the new kFactor to be applied. Re-test the dispensing and ensure the system reports an accurate volume. Multiple calibrations are often required and calibration should be tested periodically.